SR250Hi – 250 W DC UPS

No – Break ™ DC Uninterruptible Power Supply TECHNOLOGY

The New SR250Hi 250 W power supply is designed to provide DC power to lead-acid batteries for critical backup applications. All the functionality and durability has been retained with a more modern and easier to understand range of products being developed.Form factor and connectivity remains the same, so they will fit into the slots occupied by the old range – the legend continues!

No-Break ™ DC UPS systems maximise the integrity of standby battery installations, whilst optimising the life and availability of back up batteries.  They are now available with Serial and Ethernet communications options.

The No-Break ™ system is the ideal solution for:

  • Critical systems of 100W to 750W (and above using parallel operation)
  • Applications requiring continuous on-line monitoring of battery and charger status
  • Providing cost-effective management of your battery system investment

Other features include:

  • Ability to view power supply data remotely
  • Automatic or manually initiated battery condition testing to ensure availability of standby power
  • The battery condition test feature of the No-Break ™ DC system determines the condition of the back-up batteries and will provide an early warning of potential failure. This gives plant operators enough warning to replace the faulty batteries before they are required, like in the event of a mains power failure. Battery condition tests are mandatory on some fire alarm systems and are now commonly specified by consultants for critical industrial systems.

APPLICATIONS

  • Security – Access Control
  • Industrial Processes Switching Protection
  • SCADA
  • Radio Repeaters – Remote Sites

POINTS OF DIFFERENCE

  • Separate outputs for load and battery.
  • Battery detection—regular battery presence and battery circuit integrity checks.
  • Battery deep discharge protection.
  • Power loss & battery system alarms
  • No transition switching to backup battery
  • Rugged design and construction for long life and challenging environments

OPTIONAL FEATURES

  • American Input Voltage 110 VAC ( 88 – 135 VAC)
  • Fanless Option rated at 210W up to 50°C – CSR200 
  • Communication Port ( RS232 ASCII – SR485 – MODBUS RTU – SNMP, webpages)
  • Digital Input/Outputs: Customizable 2 digital inputs & 1 digital output.
  • Battery Condition Test: Option auto test enabled on start-up
  • Mounting: 19″ Rack Mount with V/I meter available, Wall mount
  • N+1 redundancy
  • Boost Charger
  • Conformal coating for rugged environments

SERIES TABLE

 ModelOutput (V) PSU Rated  (A)Charge Limit (A)Recomm. Load  (A)Peak load on power fail (A)
SR250Hi1213.81891227
SR250Hi2427.699513.5
SR250Hi3034.57.27.23.710.8
SR250Hi3641.46639
SR250Hi4855.24.54.526.7

SPECIFICATIONS TABLE

Output power250 W
Input Voltage180V – 264VAC 45-65Hz
Output Voltages12V, 24V, 30V, 36V, 48V
Voltage Adj. Range85% – 105% of Vout
Frequency45-65Hz
Overcurrent protectionConstant current limit under overload and short circuit conditions
IsolationInput – earth – 2.5KVdc
Output – earth – 500Vdc
Efficiency> 85%
Noise<1%
Operating temperature-20  to 50 °C ambient at full load
Humidity0 – 95% relative humidity non – condensing
LVDLow Voltage Disconnect
LED IndicationGreen: Batt OK
Green: Power OK
Red: Standby
Alarms RelayForm C contacts  30VDC,2A/110VDC,0.3A,125VAC, 0.5A
AUX (Activated by BCT)
POWER (main fails, PSU fails)
BATTERY (batt missing , batt low, BCT fail)
Temp. CompensationTemperature sensor on 1.7m lead with adhesive pad: -4mV/ °C / cell ± 10%
Battery Charge Current LimitCustomizable on request.
Reverse PolarityBattery reverse connection will open internal fuse (and produce alarm)
Battery MonitoringDetects for presence of battery on start up, then every 60 minutes when charge    current < 200mA
Battery Circuit ProtectionElectronic circuit breaker (ECB) operates under the following conditions:
– Low Battery Volts: Battery Voltage drops to 1.67V/cell
Overload: Max load must not exceed 110% of rated current. Peak loads must be connected to B+ & B– terminals. Not suitable for N+1 connection
Short Circuit:  <2ms, backed up by fuse
Standby ModeTurns off DC output of PSU & allows load to run off battery

OPTIONAL FEATURES

Optional Input Voltage88 – 132 VAC
Communication Port· RS232 (ASCII)
· RS485 (ASCII)
· Modbus RTU
· SNMP, Webpages
Digital Inputs/OutputsCustomizable 2 Digital Inputs and 1 Digital Output
Battery Condition Test (BCT)Option auto test enabled on start-up
Mounting· Standalone
· 19”Rack Mount . Optional V/I meter for subrack : SR-Meter
· Wall Mount
Boost ChargerCustomizable feature on request.

MODELS REPLACED BY SR250Hi

MODBUS & SNMP DOWNLOADS

SR – SRH Series – Downloads