The Ablerex MP-RT UPS is an ideal power protection solution which features industry-leading functionalities for Servers, Networks, Storage, Telecommunications, Industrial as well as Medical Diagnostic equipment.
Double Conversion On-line Technology Completely regenerates the utility power to rectify the disturbances in the utility power.The unit provides clean AC power with voltage and frequency independent from the utility.
The Hot Swappable Battery allows users with little technical knowledge to quickly change the batteries at the end of their useful service life.
MODEL | POWER | NUMBER OF BATTERIES | BATTERIES CAPACITY | RATED BATTERY VOLTAGE |
MP1000 | 1000VA | 3 | 12V/7Ah | 36Vdc |
MP2000 | 2000VA | 6 | 12V/7Ah | 72Vdc |
MP3000 | 3000VA | 6 | 12V/9Ah | 72Vdc |
Input | |
Voltage | 60/70/80~144 or 120/140/160~288Vac ( Based on load percentage) |
Frequency | 50/60Hz ±5% (Auto Sensing) |
Phase | Single Phase with Ground |
Power Factor | >0.99(Full Linear Load) |
Output | |
Voltage | 100/110/115/120/127 or 200/208/220/230/240 |
Frequency (Synchronized Range) | 3Hz or 1Hz (selectable) |
Frequency (Battery Mode) | 50Hz / 60Hz ±0.1% unless synchronized to line |
Current Crest Ratio | 3:1 |
Output Waveform | Pure Sine Wave |
Transfer Time (AC to DC) | 0 ms |
Efficiency | 90% (Line mode) |