OPUS C DC Power Systems MRC Rectifiers

Brand: Enedo

SKU: HPS-RECTIFIERS-OPUS-MRC
This product is available globally.
  • 1600W max output power (1100W for 24 VDC models)
  • Available in 24V, 48V, 60V, 110V, 125V & 220VDC standard output variants
  • Nominal 230 VAC input, 140-290 VAC
  • Internal over temperature protection
  • Can be operated as stand-alone module with and without batteries in the output

Description

OPUS C DC Power Systems MRC Rectifiers

Modular Convection Cooled Rectifiers 1600W

Efore’s MRC AC/DC rectifier series is specifically designed and optimized for demanding industrial and telecom applications. Compatible with the complete OPUS C product family, these high-efficiency fanless rectifiers offer reliable and efficient performance for telecom operators and industrial manufacturers.

The MRC rectifiers deliver 1600 watts of output power at 48V, 60, 110, 125 and 200 VDC. The 24 VDC version of the rectifier provides 1100 watts of output power. Rectifier input is single phase at 140 – 275 VAC with convection cooling.The MRC series rectifiers can be operated with either the VIDI+ system controller or as standalone modules with or without battery backup.

Main Features

  •  Natural convection cooling
  • Outputs 24V, 48V, 60V, 110V, 125V or 220VDC
  • 1600W output power
  • 1100W for 24VDC model
  • Constant output power characteristics
  • Nominal 230VAC input, 140-290 VAC
  • Active load current sharing
  • Internal overtemperature protection
  • Digital communication over CAN bus with VIDI controller
  • Flexible design with full front cabling
  • EMC: EN 300 386
  • Safety: IEC/EN 60950-1 CB certified

SERIES TABLE

ModelPower Out Max (W)Input Voltage (VAC)V1 Out Nom (V)Output Current Max (A)
MRC24-11001100180 – 2752445
MRC48-16001600180 – 2754833
MRC60-16001600180 – 2756026
MRC110-16001600180 – 27511014.5
MRC125-16001600180 – 27512512.8
MRC220-16001600180 – 2752207.2

SPECIFICATIONS TABLE

Nominal input230 VAC
Input range140 – 290 VAC (100% output power 180-275 VAC)
Startup voltage180 VAC
Reduced output power140 – 180 VAC, derating factor 1% / 1 VAC
Input frequency range45 to 65 Hz
Power factor0.99 (typical @ 230 VAC)
Input protectionMains fuse, Varistor and gas discharge tube for transient surge protection, Automatic shut-off above 290 VAC (restart at 280 VAC)
Output protectionOvervoltage shutdown Current limit / short circuit protection
Power limiting
Internal overtemperature protection
Ripple and noise< 100 mVp-p
Dimensions230 x 83 x 350 mm
Weight4.60 kg
Protection classIP20 / IEC 529
Connector, ACAppliance plug IEC 320 / 10 A male
Connector, DCFCI Twinblade TM Power IO connector
Connector, PowerCAN2 pcs RJ-45
CoolingNatural convection
Acoustic noise< 40 dB
Operating temperature-20 / +50 °C
Storage temperature-40 / +70 °C
Humidity95 % (relative humidity, non-condensing)
Altitude (max)2000 m above sea level
EMCETSI EN 300 386: 2005
EnvironmentOperation: ETS 300 019-2-3 cl T3.2
Storage: ETS 300 019-2-1 cl T1.2
Transportation: ETS 300 019-2-2 cl T2.3
SafetyIEC / EN 60950-1
ApprovalsCE, CB certified
ROHS/WEEE2002/95/EC
QualityManufacture and design conform to ISO 9001, ISO 14001