BRAVO is a compact and scalable modular inverter providing a pure sine wave AC supply. In conjunction with a DC Power system, it provides an excellent AC backup solution. It uses the latest inverter technology, providing superior energy efficiency in a compact size.The “Twin Sine Inverter” (TSI) technology eliminates all single points of failure with full scalability;
up to 32 modules in parallel and high efficiency of up to 96 % reducing operating costs.
Compatible with : TSI Nova, Media, Bravo & ECI Bravo modular inverters
Specifications | ||
48 / 120 | 125 / 120 | |
POWER | 2.5 kVA | 2.5 kVA |
INPUT | 48 / 125 Vdc | 48 / 125 Vdc |
OUTPUT | 120 Vac | 120 Vac |
Nominal voltage (DC) | 48 V | 125 V |
Voltage range (DC) | 40 – 60 V | 90 – 160 V |
Nominal current | 56 A (at 40 Vdc and 2000 W output | 25 A (at 90 Vdc and 2000 W output) |
Maximum input current (for 15 s) / voltage ripple | 84 A / <2 mV Psopho | 37 A / < 200 mV rms |
Input voltage boundaries | User selectable with T2S interface | User selectable with T2S interface |
Nominal voltage (AC) | 120 Vac (120/240 V or 120/208 V with combination of shelves) | 120 Vac (120/240 V or 120/208 V with combination of shelves) |
Voltage range (AC) | 100 – 138 Vac (without derating) (can be disabled) | 100 – 138 Vac (without derating) (can be disabled) |
Power factor | >99% | >99% |
Nominal voltage (AC*) | 120 V | 120 V |
Frequency / frequency accuracy | 50 – 60 Hz / 0.03 % | 50 – 60 Hz / 0.03 % |
EMC (immunity) | IEC 1000 – 4 | IEC 1000 – 4 |
Display | Synoptic LED | Synoptic LED |
Alarms output / supervision | Dry contacts on shelf / Standard USB port and MODBUS on T2S, optional : Candis Display / Candis TCP-IP | Dry contacts on shelf / Standard USB port and MODBUS on T2S, optional : Candis Display / Candis TCP-IP |