BC-BCW – Battery Chargers 12V & 24V: 75W-150W

Brand: HELIOS POWER SOLUTIONS

SKU: HPS-PS-BATTERY-CHARGERS-BC-BCW54
This product is available globally.
  • Universal input 90 – 264VAC.
  • Three power levels 75, 100 and 150 watts.
  • 12V & 24V systems.
  • Convection cooled – No fans.
  • Power Fail & Battery Fail alarms.

Description

The BC & BCW series battery chargers are designed for powering DC loads for battery back-up applications and available in 12V and 24V systems.

They are available in two styles: BC for panel mounting with AC Power Cord and BCW designed for wall mounting and the option to hold batteries: 2 x 7AH or 2 x 12AH batteries.

The units provide two alarms via voltage free contacts, which can be used for remote monitoring. The internal modules used are a mature power supply module that have proven extra reliable over 20 years in the field.

SERIES TABLE

ModelOutput  NomFloat V PowerCase
BC75-1212 V13.8 V75WPanel Mount
BC100-1212 V13.8 V100WPanel Mount
BC150-1212 V13.8 V150WPanel Mount
BC75-2424 V27.6 V75WPanel Mount
BC100-2424 V27.6 V100WPanel Mount
BC150-2424 V 27.6 V150WPanel Mount
BCW75-1212 V13.8 V75WWall Mount
BCW100-1212 V13.8 V100WWall Mount
BCW150-1212 V13.8 V150WWall Mount
BCW75-2424 V27.6 V75WWall Mount
BCW100-2424 V27.6 V100WWall Mount
BCW150-2424 V27.6 V150WWall Mount

SPECIFICATIONS TABLE

Input Voltage90 ~264VAC
Input Frequency 47 ~ 63Hz
Input Current75W: 1.0 / 0.5A
100W: 1.3 / 0.65A
150W: 1.9 / 0.95A
HarmonicsEN61000-3-2
Temp. Coefficient0.02% per ºC
Output VoltageRefer to table
Output CurrentRefer to table
Overload
Protection
Charger Module: Constant current with autorecovery, Battery is Fused
EfficiencyModel dependent typically 84-90%
Overvoltage
Protection
YES. Recycle input power to power on.
Parallel Operation NNO ( only for N+1 Redundancy )
Current LimitPrimary side power limited
Operating TempPrimary side ( non-latching )
Operating Temp. -10ºC to +70ºC.Derate above 50ºC @ 2.5% per ºC.
Cooling30 – 90% RH Non Condensing
Humidity    10-95% non-condensing
Ripple & Noise150mV pk-pk
SafetyUL60950-1, EN60950-1, EN50178 approval
(Internal Modules only)
InsolationInput-Output: 3Kvac,
Input-Frame Ground: 2kVAC
Output-Frame Ground: 500VAC.
EMIRadiated : EN55011-A
Conducted : EN55022-A
ImmunityIEC61000-4-2
DimensionsBC Series: 259 x 148 x 70mm (1 ~ 1.5kg )
BCW Series: 248 x 166 x 361mm ( 3 ~ 5kg )

View Datasheet