EnersineTM APF measures and monitors the entire load current through external auxiliary coupling current transformers (CT) mounted on the AC line, removes the fundamental frequency component and injects opposite phase harmonic current to cancel harmonic current in the electrical distribution system. By cancelling the harmonic currents in the circuit, there will be:
Technical Specification | |
Maximum Compensating Current Per Phase | 80ARMS per power module |
Maximum Neutral Compensating Current | 3 times of Phase Current (400V version only) |
Maximum Scalable Current Per System | 1,920ARMS (24nos. x 80ARMS power module); Different system rating can operate in parallel |
Voltage Tolerance | 400V/480V +15% / -20% (Other Voltages available with transformer) |
Nominal Frequency | 50/60Hz ± 5% (Auto Sensing) |
Power Factor Correction (Reactive Current) | Power factor correction is programmable from 0.6 lagging to 0.6 leading |
Load Balancing | Both phase to phase and phase to neutral |
CT Ratio | Programmable Primary Current: 100A~10000A Programmable Secondary Current: 1A/5A |
CT Location | Source Side: Close Loop Control or Load Side: Open Loop Control |
Response Time | Harmonic Compensation <1ms, Reactive Current Injection <20ms |
Maximum Heat losses | ≤5% at full capacity |
Compensation Ratio | 10:1 typical |
Power Electronics | 3-Level IGBT Technology |
Cooling | Forced air cooling with speed-controlled fans |
Noise Level | <65 dBA |
Interfaces | Ethernet (TCP/IP), RS-485 (Modbus RTU Protocol), USB, 3x Output Dry Contact and 1x Input Dry Contact, 1x EPO |
EMC Class Compliance | EN 55011, EN 61000-6, EN 61000-3, EN 61000-4 |
Safety Standard | Complies to EN 50178 |
Frame Dimension (WxDxH) | Maxi Frame : 600 x 900 x 1950 mm, Midi Frame : 600 x 900 x 1500 mm |
Protection Index | IP21 (Modules & Frame), other IP options available on demand |