CXC HP HV-ADIO Smart Peripheral

Brand: Alpha Technologies

SKU: CXC-HP-HV-ADIO
This product is available globally.
  • CXC HP series ADIO peripheral with flexible rack, panel, and DIN mounting options
  • Enables High Voltage (125/220Vdc) system support using the advanced CXC HP Control platform
  • I/O expansion via CAN bus for advanced site monitoring applications, including support for future growth
  • Integrated Ground Fault Detection (GFD) to alarm system fault conditions
  • On board DC-DC converter permits use with standard CXC HP low voltage controllers

Description

CXC HP HV-ADIO Smart Peripheral for 125/220Vdc rectifiers and systems

The CXC HP HV-ADIO brings advanced control and monitoring to Alpha Cordex 125/220Vdc rectifiers and systems. The HV-ADIO is part of the CXC HP series of advanced I/O peripheral incorporating flexible mounting, high accuracy, and the advanced features in the HP control platform.

The HV-ADIO provides a variety of analog inputs, digital inputs and high voltage rated relay outputs. The ADIO device is seamlessly recognized by the CXC HP control platform which also provides advanced setup wizards to create high voltage DC systems using Cordex rectifiers.

An integrated Ground Fault Detection (GFD) circuit is also provided to enable visibility to earth leakage currents. This feature can be easily disabled for operators who wish to use 3rd party GFD devices.

Cordex CXC HP controllers and ADIO peripherals ensure effortless operation and management capability to satisfy the most demanding and advanced energy system applications.

Products Compatible with CXC HP HV-ADIO Smart Peripheral

Modular Battery Charger Systems for power utilities 125 Vdc - Modular Battery Charger 48 VDC 24 VDC 12 VDC - Australia image-product-hover

The Sol Series DC Power System With Battery Backup 12V – 220VDC

HPS-WALLMOUNT-THESOLSERIES-1.1KW - Wall Mount DC System - Battery Charger for power utilities image-product-hover

The Sol Series Wall Mount 125VDC Battery Charger up to 2.2kW

SPECIFICATIONS TABLE

Electrical
Input Voltage:90 to 300Vdc
Input power:50W (125Vdc 0.4A; 220Vdc 0.2A)
Output power:30Vdc; Max 1A, 30W (For feeding low voltage
CXC HP controller)
DCCT power:±15Vdc
Features
Local alarms:Power ON (Blue)
Communications OK (Green)
Communication ports:CAN In/Out (RJ12 Offset)
Ground fault detection:1 user configurable (Adjustable up to 15mA)
on V2 input channel
Controller I/O:
Voltage inputs:2 (±300Vdc)
Current shunt inputs:1 (25 to 200mV)
DCCT current inputs:2 (±10Vdc signal)
Temperature inputs:2
Digital inputs:4 (Contact closure detect – 5Vdc Max)
Relay outputs:6 (Form C, 220Vdc 50W max)
Mechanical
Mounting:CXC HP 3U rack panel mount (0180046) or
DIN/Panel mounting
Dimensions:198H x 84W x 38D (mm)
7.8H x 3.3W x 1.5D (inches)
Weight:1kg (2lbs)
Environmental
Temperature:
Extended: -40 to 65°C (-40 to 149°F)
Humidity: 0 to 95% RH non-condensing
Elevation: -500 to +4000m (-1640 to 13124ft)
Agency Compliance
Safety:CSA C22.2 No 60950-1-03
CE marked
EMC:ETSI 300 386
Emissions:CFR47 (FCC) Part 15 Class B
ICES-03 Class B
EN55022 (CISPR 22) Class B
Immunity:EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6

View Datasheet